Conductors

Derating Current-Carrying Conductors for Conditions of Use

Derating Current-Carrying Conductors for Conditions of Use

Aug 05, 2020

If you ask a seasoned electrician how many No. 12 AWG conductors will fit into a 3/4" EMT conduit system, you may get a response such as “one more!” While this is amusing (and typically true), there are precautions that must be taken according to the NEC whenever conductors are bundled together in a raceway, cable, or even in a ditch in the earth.

» Read Article

Conduit and Cables Exposed to Sunlight on Rooftops

Conduit and Cables Exposed to Sunlight on Rooftops

Sep 25, 2019

Anyone who has been on top of a roof on a hot summer day knows what it’s like to stand in the middle of an oven. Extreme temperatures from the sun can bake everything in sight, from shingles to appliances, and even electrical conductors and conduit. Conductor insulation is meant to provide long lasting protection from expected heat due to the flow of electricity and normal environmental factors. However, excessive heat from solar radiation can damage conductors and cause premature failures.

» Read Article

Understanding Class 1, 2, and 3 Circuits: What Electricians Need to Know

Understanding Class 1, 2, and 3 Circuits: What Electricians Need to Know

Sep 07, 2018

NEC Article 725 is dedicated to specialized circuitry, different from standard power and lighting circuits. The limited power and voltage of these circuits is what makes them a separate and specialized wiring method.

» Read Article

Feeders Part 1: What is a Feeder?

Feeders Part 1: What is a Feeder?

Feb 01, 2018

In order to understand what a feeder is, it is best to start with what a feeder is not. The conductors between the utility service point and the service disconnecting means are service conductors, not feeder conductors. Special service conductor rules apply because these conductors do not have short-circuit or ground-fault...

» Read Article

Article 90: Simple But Important Changes

Article 90: Simple But Important Changes

Mar 23, 2017

When reading a book, how often do we skip past the introduction and start with the chapters that interest us? That happens to those of us that use the NEC as well, but understanding the introduction to the code in Article 90 is key to properly applying the technical requirements...

» Read Article

Feeder Conductor Ampacity

Feeder Conductor Ampacity

Jan 24, 2017

The conditions of use must be considered when determining the minimum size of a feeder conductor. A continuous load, such as the lighting load in a store building, generates heat in the feeder conductor that must be compensated for. Ambient temperatures above 86oF or more than...

» Read Article

Feeders Part 2: Overcurrent Protection

Feeders Part 2: Overcurrent Protection

Dec 06, 2016

The general rule in 215.3 is that a feeder overcurrent device shall have a rating not less than the noncontinuous load plus 125% of any continuous loads supplied by the feeder. Unless permitted for specific applications, such as motor circuits, the rating of the feeder overcurrent device is selected as...

» Read Article

Securing & Supporting Cables & Raceways Part Two | JADE Learning

Securing & Supporting Cables & Raceways Part Two | JADE Learning

Jun 21, 2016

The requirements for securing and supporting are similar in intent, but there are differences. Securing is done by installing a mechanical means of attachment to the cable and attaching it to a stationary structural member so the cable does not move. This will prevent the cable or conduit from becoming loose and pulling away from a box or fitting. Support requires a mechanical means to prevent the cable from sagging or drooping which may cause damage to the cable and create a hazard. A cable may remain loose while its support is maintained.

» Read Article

Securing and Supporting Cables and Raceways Part One | JADE Learning

Securing and Supporting Cables and Raceways Part One | JADE Learning

May 20, 2016

The 2014 NEC is clear about how cables and raceways must be supported. The general rule in 300.11(A) is that raceways, cable assemblies, boxes, cabinets and fittings shall be securely fastened in place. Cables cannot be used as a means of support for other cables, raceways, or nonelectrical equipment, per 300.11(C)...

» Read Article

Table 250.102(C)(1) Sizing Grounded Conductors, Bonding Conductors, and Bonding Jumpers

Table 250.102(C)(1) Sizing Grounded Conductors, Bonding Conductors, and Bonding Jumpers

Apr 20, 2016

Supply-Side grounded and bonding conductors are sized from Table 250.102(C)(1) in the 2014 NEC. In earlier Codes, all these conductors, as well as the Grounding Electrode Conductor, were selected from Table 250.66. Table 250.102(C)(1) from the 2014 NEC. It is very helpful to have a separate Table for selecting the size of...

» Read Article

SE Cable Ampacity According to the 2014 NEC

SE Cable Ampacity According to the 2014 NEC

Feb 25, 2016

Properly sizing an SE cable installed in thermal insulation requires a careful examination of the Code. Section 338.10(B)(4)(a) is all about interior installations of SE cables and states: Where installed in thermal insulation the ampacity shall be in accordance with the 60°C (140°F) conductor temperature rating. The maximum conductor temperature...

» Read Article

Replacing Two-Wire Receptacles

Replacing Two-Wire Receptacles

Jan 28, 2016

Upgrading wiring in older homes usually includes replacing old two-wire, non-grounding type receptacles. Replacing a two-wire receptacle with a grounding-type receptacle and not providing an equipment ground or GFCI protection is a serious NEC violation. Extending a two-wire circuit without an equipment ground is also prohibited, even if protected by...

» Read Article

Pool and Spa Wiring Part II

Pool and Spa Wiring Part II

Aug 26, 2015

Here is a list of the most common electrical mistakes made when installing a hot tub outdoors

» Read Article

Pool and Spa Wiring Part I

Pool and Spa Wiring Part I

Jul 20, 2015

Here are some common items that can cause the electrical inspection to fail at swimming pools.

» Read Article

Passing an Above-Grid Ceiling Inspection

Passing an Above-Grid Ceiling Inspection

Dec 29, 2014

Here are the 6 most common violations that inspectors see in an above-grid ceiling inspection:

» Read Article

Applying NEC 310.15(B)(7)

Applying NEC 310.15(B)(7)

Nov 26, 2014

The fact that the table was removed is neither here nor there. More importantly is how to apply the 83% and when the Code section allows us to use it. Applying 310.15(B)(7) to one-family dwellings or the individual dwelling units of two-family and multi-family dwellings, has always been dependent on a few important factors:

» Read Article

Identification of Grounded Conductors

Identification of Grounded Conductors

May 23, 2013

Today John Hauck and David Burtt discuss the identification of grounded conductors according to the 2011 National Electrical Code. This is part 2 of a 3 part series on identifying conductors. How are grounded conductors required to be identified?200.6(A). In sizes No. 6 AWG and smaller, an insulated grounded...

» Read Article

Identification of Ungrounded Conductors

Identification of Ungrounded Conductors

May 16, 2013

Today John Hauck and David Burtt discuss the identification of ungrounded conductors according to the 2011 National Electrical Code. This is part 1 of a 3 part series on identifying conductors. Does the National Electrical Code have a required color code? No. The National Electrical Code does not have a...

» Read Article

Bonding Corrugated Stainless Steel Tubing (CSST) Gas Pipe

Bonding Corrugated Stainless Steel Tubing (CSST) Gas Pipe

Apr 04, 2013

Corrugated stainless steel tubing (CSST), is used to convey flammable gas inside or outside of a building. It is not mentioned in the 2011 NEC by name, but Informational Note No. 2 to 250.104(B) cites NFPA 54, the National Fuel Gas Code, as a source for additional information for gas...

» Read Article