Articles

Multiwire Branch Circuits NEC 210.4

Mar 08, 2013

A common application of multiwire branch circuits as described in section 210.4 is for a 120/240-volt, single-phase system where three wires do the work of four, the two ungrounded conductors sharing a single neutral. In a 20 amp multiwire branch circuit if the two ungrounded conductors each carry 15 amps, some people think the neutral carries 30 amps, or the combined total of the current on each ungrounded conductor.

Electrical Continuing Education Now Required in Alabama

Feb 06, 2013

As of January 1, 2013, the Alabama Board of Electrical Contractors has adopted Rule 303-X-5 that requires continuing education for all licensed electrical contractors and provisional electrical contractors.

Changes to the 2012 Edition of NFPA70E

Jan 04, 2013

Here is a brief look at ten important changes in the 2012 Edition of NFPA 70E.

Field Marking Available Fault Current- NEC 110.24

Jan 03, 2013

Marking the maximum available current and the calculation date on the service equipment makes it much easier to confirm the interrupting rating of the equipment.

Explore key topics: